|
|
|
Troubleshooting Guides
Click one of the links below to skip to the troubleshoot tips for that topic.
|
|
|
|
Basic troubleshooting for split systems:
- First make sure that the thermostat is set lower than the actual
room temperature. The selector switch must be on "cool."
If the thermostat is programmable, be certain it has fresh batteries.
- Check for power by moving the fan switch from "auto" to "on."
If the blower runs, there is power. If nothing happens, a control
is burned out or power is disconnected. If the system uses a furnace
for heat, check that the emergency switch is on. If you are familiar
with the fuse or circuit breaker panel, check for blown fuses
or tripped breakers. Correct the problem one time only. If it
repeats, call for service.
- With the selector switch on cool and the fan switch on auto,
move the thermostat well below room temp. If the blower runs but
the condenser (outdoor unit) does not, check the circuit breaker
panel. If the breaker is on, examine the condenser. Some have
a high pressure cut out. It is a button sticking out of the cabinet,
usually near the refrigerant lines. Push it in as far as it will
go to reset it.
- If both units are running and no cooling is taking place, touch
the larger of the two copper lines exiting the condenser. If it
is warm, the system is out of freon or the compressor is down.
If the line is frozen or iced over, there is an air flow problem
inside, such as clogged filter or too many registers closed or
an object covering the return duct. A low freon charge will also
cause a freeze-up. Shut the system down and let it thaw out completely.
If it freezes up again, call for service.
- If the unit is in the basement and has a condensate pump, the
control wire for the condenser might be wired through a safety
switch on the pump. Check to see if the pump is plugged in and
operable.
- If the unit is in the attic, there could be a float switch in
the air handler or in the safety pan that will shut the condenser
off if the drain is clogged. Water around the unit is evidence
of trouble. Call for service.
Back to Top
|
|
|
Basic troubleshooting:
- The thermostat must be set higher than the actual room temperature.
If the thermostat is programmable, be certain it has fresh
batteries.
- If there is central air, or the system is zoned, make sure
the selector switch is on heat.
- If you are familiar with the fuse or circuit breaker panel,
check for blown fuses or tripped breakers. Correct the problem
once. If it repeats, call a serviceman.
- Do not attempt to service the controls inside the cabinet.
Deadly high voltage conditions exist.
Back to Top
|
|
|
| Troubleshooting falls into two categories: grid failure or power failure. Excess
dirt or a large object stuck in the grids will cause an electrical
short. A loud snapping noise will sometimes indicate this problem.
If cleaning does not stop the snapping and the grids are bone
dry, inspect the fine wires stretched across the terminals.
If they are white from oxidation, gently run an old soft toothbrush
up and down them once, then rinse and dry again.
Most electronic air cleaners have a light to show operating power.
If the light is not on when the system is running and the
switch is on, there are three possibilities: the power pack
has burned out, the power to it has been disconnected, or
the unit has a pressure switch to sense air flow and charge
the grids and it has failed. Either repair means opening up
the power pack, exposing dangerously high voltage.
This task should be left to a qualified technician.
Back to Top
|
|
|
Basic troubleshooting:
- Check that the thermostat is set higher than the actual room temperature.
If you have a programmable thermostat, make sure it has
fresh batteries.
- If equipped with central air, or the system is zoned, make
sure the selector switch is on heat.
- Check the emergency switch ( usually a red switch plate at the
top of the cellar stairs or on the side of the furnace)
to see that it is on.
- If you are familiar with the fuse or circuit breaker panel,
see if the fuse is burned or the breaker tripped. Correct
the problem once. If it repeats, call a serviceman.
- On standing pilot furnaces, the burner will not light if the
pilot has gone out. If you are not familiar with the function
of the gas valve or lighting the pilot, call for service.
- Furnaces with electronic ignition have a sequence of safety steps
the burner takes to light. Information is usually attached
to the inside of the burner or blower access door. Follow
the procedure according to the manufacturer's guidelines
to avoid the risk of fire or explosion.
- Do not disconnect any piping to check for gas supply. An instrument
is used to check for pressure, and checking it should be
done by a qualified serviceman.
- If the furnace is vented through PVC (white plastic pipe) out
the side of the building, examine the ends of the pipe or
pipes outside. Blockage of any kind will cause a shutdown.
Back to Top
|
|
|
Basic troubleshooting:
- Be certain that the thermostat is set higher than the actual
room temperature and the selector switch is set to heat
if in heating mode, or that the thermostat is set lower
than room temperature and the selector switch is on cool
if air conditioning is desired. If the thermostat is programmable,
make sure it has fresh batteries.
- An easy test for power is to move the fan switch from "auto"
to "on." If the blower runs there is power to the unit.
If you are familiar with the fuse panel or circuit breaker
panel, check for blown fuses or tripped breakers. Correct
the problem once. If it repeats, call for service.
- Check the water supply if fed from a well. A clogged filter or
strainer may trip safety switches that will not allow the
unit to run without water.
- Because the controls are mounted internally and high voltage connections
are exposed if the cabinet is opened, only a qualified technician
should access them.
Back to Top
|
|
|
Basic troubleshooting:
- Make certain that the thermostat is set higher than the actual
room temperature and the selector switch is on heat if heat
is needed, or that the thermostat is set lower than the
actual room temp and the switch is on cool if air conditioning
is desired. If the thermostat is programmable, be certain
the batteries are fresh.
- Test for power to the air handler by moving the fan switch from
"auto" to "on." If the blower runs, the air handler
is functional. If nothing happens, check the circuit breakers
on the air handler cabinet and the breakers or fuses in
the main panel. If any breakers are tripped, reset them
once. If they trip again do not reset them. Deadly high
voltage conditions exist inside the air handler cabinet
and inside the access panel of the condenser. Let a qualified
serviceman open them.
- If the air handler runs constantly but cannot satisfy the thermostat
setting, it is possible the backup heat is running but the
condenser is not. Some condensers have the high pressure
cut-out switch externally accessible. Look for a button
sticking out of the cabinet in the vicinity of the refrigerant
pipes. Press it in. If the machine starts up, the head pressure
got too high, possibly from turning on and off too quickly,
too much or too little refrigerant, or an electrical interruption.
As the unit ages, the switch can weaken and pop easily.
If the condition repeats itself often, have a serviceman
check it.
- Because all the controls are internally mounted and high voltage
wiring is exposed, only a serviceman should open panels.
Back to Top
|
|
|
Basic troubleshooting:
- Make sure that the thermostat is set higher than the actual room
temperature. If the system has central air, or the system
is zoned, make certain that the selector switch is on heat.
If the thermostat is programmable, fresh batteries might
be needed. Hot water must circulate through the pipes and
coil before heat can be produced, so allow time for this
to take place.
- Make sure that the emergency switch (usually a red switchplate
at the top of the basement stairs or at the side of the
boiler), is on. There might be a switch on the air handler
to check. An oil burner will have a red button on the protecto
relay mounted on the burner. Press it only once. If it does
not fire and continue to run, call for service. Resetting
the button repeatedly can create an explosive condition.
- If the system has central air, move the fan switch on the thermostat
from "auto" to "on." If the blower runs, it proves
power at the air handler. If warm air flows out of the registers,
the aquastat could be out of adjustment or the time delay
is malfunctioning. If the blower does not run and there
is power to the air handler, a control has burned out or
the blower motor needs checking. Do not put fingers or hands
in the blower. Aside from sharp edges, it could start up
unexpectedly and cause a serious injury.
- Many air handlers have a safety switch that shuts off power if
the door is removed. Check that the door is correctly installed.
Back to Top
|
|
|
Basic troubleshooting:
- First check that the thermostat is set higher than the actual
room temperature. If you have a programmable thermostat,
check that it has fresh batteries.
- If equipped with central air, or the system is zoned, make
certain the selector switch is on heat.
- Check that the emergency switch (usually a red switch plate at
the top of the cellar stairs or on the side of the furnace)
is on.
- If you are familiar with the fuse or circuit breaker panel,
see if the fuse is burned or the breaker is tripped. Correct
the problem once; if the fuse blows or breaker trips again,
call a serviceman.
- If you can access the burner, check the red button on the protecto
relay. Older furnaces will have a stack limit switch mounted
on the smoke pipe that connects the furnace to the chimney.
Push the button one time only. Repeated attempts to fire
the burner without ignition can create an explosive condition.
If the burner fails to fire and continue running on its
own, call for service.
Back to Top
|
|
|
Basic troubleshooting:
If the furnace does not have backup heat, thens controls are minimal,
consisting of a thermostat, relay and fan. Most furnaces with
backup heat will have a second thermostat to control the auxiliary
heat.
If the furnace has backup heat that will not operate, try the following:
- First check that the thermostat is set higher than the actual
room temperature. If you have a programmable thermostat,
check that it has fresh batteries.
- If equipped with central air, or the system is zoned, make
certain the selector switch is on heat.
- Check that the emergency switch (usually a red switch plate at
the top of the cellar stairs or on the side of the furnace)
is on.
- If you are familiar with the fuse or circuit breaker panel,
see if the fuse is burned or the breaker is tripped. Correct
the problem once; if the fuse blows or breaker trips again,
call a serviceman.
- If you can access the burner, check the red button on the protecto
relay. Older furnaces will have a stack limit switch mounted
on the smoke pipe that connects the furnace to the chimney.
Push the button one time only. Repeated attempts to fire
the burner without ignition can create an explosive condition.
If the burner fails to fire and continue running on its
own, call for service.
Back to Top
|
|
|
|
|
|
|
|
Copyright © 1999 Warmair.com, Inc.
Back to Main Page
Email this page to a friend
|
|
|